Arc-suppression coil neutral earthing

Arc-suppression coil neutral earthing

Place of Origin : China
Brand Name : THT
Certification : ISO9001
Packaging Details : woodencase
Delivery Time : 45days
MOQ : 1 set
Contact Now

Company information

We are a leading manufacturer of theneutral grounding electric equipmentsin China and we have many years experience in this line of business. Our products are also exported to Asia, Africa, Russia, the United States, and the Middle East.

We have cooperation relationship with ABB, Siemens, TEBA, HYOSUNG,Alston and so on, we want to build a long time cooperation relationship with your company.

System Description

THT-PXHK(C) system is mainly used for 6KV-66KV neutral ungrounded power grid and also widely applies to high voltage distribution networks in mining , coal , chemical industry and larger cities .

With normal grid operation, the system provides real-time monitoring of network capacitive current. When occurs single-phase grounding, it will automatically enter compensation state and implement optimal compensation for the grid capacitive current. The fault residual current will be less than 5A, which can effectively suppress the arc over-voltage, thus prevent failures arising like phases short circuit etc. The system can be customized to set for ideal state as per user requirements.

Model description

System Composition

THT-PXHK system consists of three units: microcomputer control cabinet, biasing magnetic arc-suppression coil body, grounding transformer (optional to users). The grounding transformer and arc suppression coil can either dry or oil immersed. The microcomputer control cabinet is with standard screen, which includes automatic tracking compensation controller, dashboard and rectifier etc.

Table 1-1 Model and technical data


6KV arc suppression coil

10KV arc suppression coil

35KV arc suppression coil

Type Code

Max. Compensation Current

Type Code

Max. Compensation Current

Type Code

Max. Compensation Current

THT-PXHK—6/10

10

THT-PXHK—10/10

10

THT-PXHK—35/10

10

THT-PXHK—6/20

20

THT-PXHK—10/20

20

THT-PXHK—35/20

20

THT-PXHK—6/30

30

THT-PXHK—10/30

30

THT-PXHK—35/30

30

THT-PXHK—6/40

40

THT-PXHK—10/40

40

THT-PXHK—35/40

40

THT-PXHK—6/50

50

THT-PXHK—10/50

50

THT-PXHK—35/50

50

THT-PXHK—6/60

60

THT-PXHK—10/60

60

THT-PXHK—35/60

60

THT-PXHK—6/70

70

THT-PXHK—10/70

70

THT-PXHK—35/70

70

THT-PXHK—6/80

80

THT-PXHK—10/80

80

THT-PXHK—35/80

80

THT-PXHK—6/90

90

THT-PXHK—10/90

90

THT-PXHK—35/90

90

THT-PXHK—6/100

100

THT-PXHK—10/100

100

THT-PXHK—35/100

100

THT-PXHK—6/120

120

THT-PXHK—10/120

120


THT-PXHK—6/140

140

THT-PXHK—10/140

140

THT-PXHK—6/160

160

THT-PXHK—10/160

160

THT-PXHK—6/180

180

THT-PXHK—10/180

180

THT-PXHK—6/200

200

THT-PXHK—10/200

200

Compensation Principle
Electric power industry standard DL/T 620-1997 “AC electric equipment overvoltage protection and insulation coordination” provides: For the 3KV- 10KV system indirectly connect to generator and 35KV, 66KV system, when single phase ground-fault capacitive current doesn’t exceed the following values, should use non-grounding method , when exceed the following values and need to run under ground-fault conditions , should use arc suppression coil grounding method:
1,3KV- 10KV overhead line System constructed by concrete or metal tower and all 35KV, 66KV system, 10A

2, 3KV-10KV overhead line system constructed by non-concrete or non-metal tower:

1) 3KVand 6KV, 30A

2) 10KV, 20A

3, 3KV-10KV cable system, 30A


Be Aware of Notices

1, After installation, shall carry out strict inspection on the system, to ensure everything is all right.

2, Equipment installation, wiring, test, maintenance shall be undertaken by qualified professionals, ensure no power in equipment prior to installation.

3, Whenever occurs single phase grounding, not allowed to operate or manually adjust the arc suppression coil on the bus cable.

4, Whenever occurs single phase grounding, not allowed to switch off controller and controller AC and DC power supply.

5, Don’t operate if any of following circumstances happen when turning on isolation switch between arc suppression coil and neutral point:

1) Single phase grounding happens, and sounds hum from arc suppression coil

2) Neutral point displacement voltage is greater than 50% phase voltage.

6, Single phase grounding happens, monitor and record the following data if possible:

1) Operation of grounding transformer and arc suppression coil.

2) Parameters displayed on the microcomputer screen: capacitive current, residual current, out-of-resonance

degree,neutral point voltage and current etc.

3) The start and end time about the occurrence of single phase grounding.:

4) The connection lines and single phase grounding reason.

5) Weather Conditions.


Product Tags:

Arc-suppression

      

Arc-suppression coil

      

Arc-suppression coil neutral earthing

      
China Customized Inflatable Bumper Ball Game Bubble Adult Grass CE supplier

Arc-suppression coil neutral earthing Images

Inquiry Cart 0
Send your message to this supplier
 
From:
To: Baoding Tianwei Hengtong Electric Co.,Ltd
Subject:
Message:
Characters Remaining: (0/3000)
 

Home| Products| Suppliers| Quality Suppliers| Site Map |About Us |Contact Us |Help |关于我们 |联系我们

Copyright © 2009 - 2019 entremaqueros.com. All rights reserved.